Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T11CM03197
Parcel: 12703001A

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T11CM03197
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/16/2011 DAVE MANN FIRE REVIEW Approved
11/16/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PREVIOUS COMMENT 3: ADD THE ICC/ANSI A117.1-2003 TO THE CODES USED ON SHEET G1.0.
2. PREVIOUS COMMENT 5: ADD A REFERENCE IN THE NOTE TO THE SPECIFIC DETAILS ON SHEET A9.1.
3. PREVIOUS COMMENT 25: SHEET P1.3 (DETAIL 1) INDICATES A BRACED PLATFORM FOR THE WATER HEATER SUPPORT. REFERENCE IS MADE TO DETAIL 1/A9.4, BUT DOES NOT MATCH THAT DETAIL. REVISE 1/P1.3.
4. PREVIOUS COMMENT 28: ALL DEFERRED SUBMITTALS MUST BE APPROVED IN WRITING BY RON BOOSE (BUILDING OFFICIAL) BEFORE THOSE SUBMITTALS WILL BE REVIEWED. RON.BOOSE@TUCSONAZ.GOV.
5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
11/17/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
11/17/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The specified backflow preventer assembly, BP1, is a double check valve assembly, not a reduced pressure zone backflow assembly. It is suitable for your intended use but unlike the reduced pressure zone backflow assembly, it does not have a drain. If the backflow assemblies (BP1 and BP2) are located in a location remote from the appliance to which they are connected, provide a permanent label for each valve assembly per Section 603.3.2, UPC 2006. Each backflow assembly shall be installed with access and clearances per Section 603.3.4, UPC 2006. [Original comment: Specify the type of backflow prevention device required for the water connection to each appliance (note #1, sheet P1.2). Reference: Sections 602.3, 603.0, and Table 6-2, UPC 2006.]
2. Revise the size of the portion of the vents between the cleanout and the trap arm of the floor sinks to comply with the requirements of Table 7-6, UPC 2006 (i.e. a 3" drain line requires a minimum cleanout size of 2.5"). [Original comment: Show the size of the under-floor portion of the vents for the floor sinks located in the equipment room and in the sales floor area. The size of that portion of the vent shall comply with the cleanout size requirements of Table 7-6, UPC 2006. Reference: Section 707.11, UPC 2006.]
3. Comment not addressed; the specified hydromechanical grease interceptor requires an external flow control device which cannot be used with fixtures that are roughed-in at floor level, such as the mop sink. [Original comment: Each fixture that is connected to a hydromechanical grease interceptor requires a flow control device unless the grease interceptor is equipped with an integral flow control device. Reference: Section 1014.2.1, UPC 2006.]
11/17/2011 ROBERT SHERRY WATER REVIEW Approved
11/17/2011 RONALD BROWN ZONING HC REVIEW Passed
11/21/2011 GERRY KOZIOL WWM REVIEW Denied NEED TOIDENTIFY ALL WW PLUMBING FIXTURES REMOVED FOR CREDIT - NEED WW 5TH FL CREDIT EVALUATION - 740-6602 OR 740-6606
NEED PCRWRD 3RD FL CAPACITY REVIEW- KURT STEMM 740-6607
NEED WW REVIEWOF LOCATION/METHOD OF CONNECTION TO PUBLIC SEWER - CHAD AMATEAU 740-6547
12/01/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
12/02/2011 PAUL MACHADO ENGINEERING REVIEW Approved
12/05/2011 TERRY STEVENS ZONING REVIEW Denied 11/05/2011

Development Services Department
Zoning Review Section

Terry Stevens
Lead Planner

Comments:

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved development plan. Please submit two copies of the approved and stamped development, landscape, and NPPO plans with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved site/development plan. Additional comments may be forthcoming.