Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T11CM03190
Parcel: 136261300

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM03190
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/06/2011 MARTIN BROWN FIRE REVIEW Approved
10/18/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEETS A1, A2, A3, AND A4 (BUSINESS AND TRAINING): THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THESE SHEETS.
2. SHEETS A1 (BUSINESS AND TRAINING); PROJECT DATA: THE CONSTRUCTION TYPE IS LISTED AS IIA (THIS IS PROTECTED CONSTRUCTION), THEN LISTED AS UNPROTECTED. SHOULD THIS BE TYPE IIB CONSTRUCTION? CLARIFY.
3. SHEETS A1 (BUSINESS AND TRAINING); PROJECT DATA: THE ACCESSIBILITY CODE REFERENCE SHOULD BE ICC/ANSI A117.1-2003. REVISE.
4. SHEETS A1 (BUSINESS AND TRAINING): PROVIDE ENLARGED PLANS OF THE RESTROOMS (SPECIFIC TO THIS JOB, NOT 'TYPICAL'), AND ENLARGED RESTROOM DETAILS, INDICATING ALL HEIGHTS, LENGTHS, AND LOCATIONS OF ALL GRAB BARS, PAPER DISPENSER, AND WATER CLOSET PER ICC/ANSI A117.1-2003, CHAPTER 6.
5. SHEETS A1.1 (BUSINESS AND TRAINING); SITE PLAN: IT IS UNCLEAR WHERE THIS PROJECT IS LOCATED ON THE SITE PLAN. INDICATE.
6. SHEETS A4 (BUSINESS AND TRAINING); BRACING AT THE TOP OF PARTITION WALLS: PROVIDE AN ENLARGED DETAIL FOR THE CONNECTION OF THE TOP OF THE WALL BRACE TO THE STRUCTURE ABOVE WHEN THE WALL IS PERPENDICULAR TO THE STRUCTURE (SIMILAR TO PARALLEL).
7. SHEET A1 (TRAINING); PROJECT DATA: THE TRAINING FACILITY FALLS UNDER THE OCCUPANCY CLASSIFICATION OF BUSINESS PER THE IBC SECTION 304. REVISE.
8. SHEETS M1 (BUSINESS AND TRAINING); EXHAUST FAN DETAIL: PROVIDE ENLARGED DETAILS OF HOW THE EXHAUSE FAN SUPPORT RODS ARE CONNECTED AT THE ROOF.
9. GENERAL: THE IBC TABLE 2902.1 REQUIRES ONE HIGH/LOW DRINKING FOUNTAIN, OR A SINGLE POINT-OF-USE WATER DISPENSER. INDICATE ON THE PLAN.
10. SHEETS A2 (BUSINESS AND TRAINING); FLOOR PLAN: PROVIDE A NORTH ARROW ON THE PLAN.
11. GENERAL: THERE ARE TWO SEPARATE SETS OF 'A' SHEETS WITH DIFFERENT INFORMATION. PLEASE CLARIFY (PROVIDE COMPLETE FLOOR PLAN FOR TRAINING AND BARBER AREAS, OR MATCH LINES, OR APPLY FOR SEPARATE PERMITS).
12. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
10/24/2011 RMYERS1 WATER REVIEW Denied 1. SHOW THE LOCATION AND SIZE OF THE WATER METER, AND THE REDUCED PRESSURE BACKFLOW PREVENTER.
10/24/2011 RICK MYERS PLUMBING-COMMERCIAL REVIEW Denied 1. INCLUDE ON THE COVER SHEET, THE STREET ADDRESS, THE PHYSICAL LOCATION, AND THE SUITE NUMBER OF THE CONSTRUCTION SITE. 2. SHOW HOW THE WATER IS TEMPERED AT THE PUBLIC USE LAVATORY. REFERENCE: 416.5 2006 IPC. 3. INCLUDE HOW THE DOMESTIC WATER SYSTEM IS TO BE STERILIZED. REFERENCE: 610.1 2006 IPC. 4. INCLUDE THE MATERIAL TYPE FOR DWV PIPING ON THE PLUMBING GENERAL NOTES. 5. WASHER BOX SUPPLIES TO HAVE WATER HAMMER PROTECTION. REFERENCE: 604.9 2006 IPC.
10/24/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that a notation shall be placed beneath the seal, either written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008).
2. Revise the font size used on the drawings to a minimum height of 3/32-inch. Reference: Section 106.1.1, IBC 2006.
3. Specify the minimum resistance (R-value) of the duct insulation to be used on this project. Reference: Section 503.2.7, IECC 2006, as amended by the City of Tucson.
11/01/2011 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Denied For questions about this electrical plan review please contact Dan Santa-Cruz 520-909-5173 or LeeRay 909-5154.

1) Minimum font size accepted in the City of Tucson is 3/32" please adjust

2) You have provided two separate 'E1' pages with differing information please clarify (provide complete floor plan for training & barber area, or match lines, or apply for separate permits).

3) Both of your E1 pages indicate there are additonal E1.1-- E1.3 pages, where are these?
11/02/2011 GERRY KOZIOL WWM REVIEW Denied NEED 2ND PERMIT FOR TRAINING ROOM
NEED 5TH FLOOR CREDIT EVALUATION

Final Status

Task End Date Reviewer's Name Type of Review Description
11/15/2011 CPIERCE1 OUT TO CUSTOMER Completed
11/15/2011 SUE REEVES REJECT SHELF Completed