Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T11CM03188
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/12/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET PE1.0; DETAIL 1: THE DETAIL REFERENCES ARCHITECTURAL PLANS FOR THE CONNECTION OF THE WATER HEATER BRACKET TO THE WALL. THE ARCHITECTURAL SHEET DOES NOT INDICATE THAT CONNECTION. PROVIDE THE CONNECTION. |
| 10/12/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 10/12/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | WH on plunb sheet 4500w,208/3 p not 120v. |
| 10/13/2011 | DROBEY1 | WWM | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/13/2011 | DELMA ROBEY | OUT TO CUSTOMER | Completed |