Permit Number: T11CM03188
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM03188
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/05/2011 STEVE SHIELDS ZONING REVIEW Approved
10/05/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
10/05/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied New Electric water heater not on electrical plans,where would it receive it's power ?

Ray T Majuta
10/05/2011
10/05/2011 ROBERT SHERRY WATER REVIEW Approved
10/05/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied Please provide structural calculations and structural details for wall mounted water heater. Provide wall support analysis also.
10/05/2011 PAUL MACHADO ENGINEERING REVIEW Approved
10/05/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide an indirect connection for the sanitizing compartment of the 3-compartment sink with a direct waste connection for the wash and rinse sections of the 3-compartment sink. Reference: Section 802.1, IPC 2006.
10/05/2011 DAVE MANN FIRE REVIEW Approved
10/05/2011 RONALD BROWN ADA REVIEW Passed
10/05/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/12/2011 CAGUILA1 WWM REVIEW Needs Review