Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/05/2011 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
10/05/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
10/05/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | New Electric water heater not on electrical plans,where would it receive it's power ? Ray T Majuta 10/05/2011 |
10/05/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
10/05/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | Please provide structural calculations and structural details for wall mounted water heater. Provide wall support analysis also. |
10/05/2011 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
10/05/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide an indirect connection for the sanitizing compartment of the 3-compartment sink with a direct waste connection for the wash and rinse sections of the 3-compartment sink. Reference: Section 802.1, IPC 2006. |
10/05/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
10/05/2011 | RONALD BROWN | ADA | REVIEW | Passed | |
10/05/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
10/12/2011 | CAGUILA1 | WWM | REVIEW | Needs Review |