Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T11CM03177
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/13/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET CD01; PROJECT DATA: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE. 2. SHEET CD01; PLUMBING FIXTURES: IT IS NOTED THAT THERE IS A DRINKING FOUNTAIN IN THIS BUILDING. SHOW ON THE PLAN (MUST BE A HIGH/LOW DRINKING FOUNTAIN OR A SINGLE POINT OF USE WATER DISPENSER). 3. SHEET D02.2; HARDWARE SPECIFICATIONS: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE. 4. SHEET D02.2; WALL TYPE LEGEND: FOR NEW INTERIOR PARTITION (W1), PROVIDE A DETAIL FOR BRACING THE TOP OF THE WALL TO THE STRUCTURE ABOVE TO RESIST LATERAL LOADS REQUIRED BY THE IBC SECTION 1607.13. INCLUDE THE BRACING SIZE AND SPACING, AND THE CONNECTION OF THE BRACING TO THE TOP OF THE PARTITION WALL AND TO THE STRUCTURE ABOVE. 5. SHEET D05.2; FLOORING TRANSITIONS: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE. 6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
12/14/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
12/14/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
12/14/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide the minimum plumbing facilities required by Table 2902.1, IBC 2006, for business occupancy (a bottled water dispenser is not recognized as a substitute for a drinking fountain). Reference: Sections 1109.5 and 2902.1, IBC 2006. 2. Provide tempered water to the lavatories through the use of an approved temperature limiting device that conforms to ASSE 1070. Reference: Section 416.5, IPC 2006. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
12/20/2012 | CPIERCE1 | APPROVAL SHELF | Completed |
12/20/2012 | CPIERCE1 | OUT TO CUSTOMER | Completed |