Permit Number: T11CM03177
Parcel: 12708187F

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM03177
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/04/2011 MICHAEL ST. PAUL ZONING REVIEW Approved
10/04/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide information on the sequence of operation for the restroom exhaust fans to show that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2006.
2. Provide calculations demonstrating adequate ventilation. Reference: Section 403.3, IMC 2006, as amended by the City of Tucson.
10/04/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied 1. All lettering and numbering to be minimum 3/32" per Submittal Requirements.
2. See Mechanical Plans Examiner comments regarding supply air and exhaust, must be so that when air supplied exhaust on, show electrically how this will be done.

Ray T Majuta,
Elect Pln Ck,
PDSD, C of Tuc,
10/3/11
Ray.majuta@tucsonaz.gov
10/04/2011 ROBERT SHERRY WATER REVIEW Approved
10/04/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Please revise all sheets that have lettering sizes (upper and lower case) less than 3/32" in height.
2. Please provide last approved site plan.
3. Please provide structural calculations and details for the wall mounted water heater.
END OF REVIEW
10/04/2011 JASON GREEN ENGINEERING REVIEW Approved
10/04/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show how the mounting shelf for the water heater is connected to the building structure. Reference: Sections 106.3.1 and 301.2, IPC 2006.
2. Provide a vacuum relief valve for bottom-fed storage-type water heaters. Reference: Section 504.2, IPC 2006.
3. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference: Section 504.3, IECC 2006.
10/04/2011 DAVE MANN FIRE REVIEW Approved
10/04/2011 RONALD BROWN ADA REVIEW Passed
10/04/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed