Permit Number: T11CM03155
Parcel: 13214078K

Address:
3737 S PARK AV

Review Status: Completed

Review Details: REVISION - - 3RD

Permit Number - T11CM03155
Review Name: REVISION - - 3RD
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/03/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide dimensions from the propoane tank discharge relief valve, vent discharge, and the filling connection to the fresh air intake of the packaged A/C units. Reference: Table 6.3.8, NFPA 58-2011.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/26/2013 SHANAE POWELL OUT TO CUSTOMER Completed