Permit Number: T11CM03155
Parcel: 13214078K

Address:
3737 S PARK AV

Review Status: Completed

Review Details: REVISION - - 2ND

Permit Number - T11CM03155
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/12/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved T11CM03155

1. The electrical panel shows 2 water heaters at 120 volt 20 amps, the plumbing plan shows 3 at 208 volt 14.6 amps ?

Ray Majuta
Elec Pln Review
7/12/2013
07/12/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
07/12/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
07/12/2013 MARTIN BROWN FIRE REVIEW Approved Revised plans (sheet P1) now indicate addition of LPG tank.
Will need to show revised site plan showing size of tank (in gallons) and exact location on site, with dimension to buildings, property liones, etc.
Be advised a seperate permit may be required for the installation of the tank.