Permit Number: T11CM03155
Parcel: 13214078K

Address:
3737 S PARK AV

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T11CM03155
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/01/2013 MARTIN BROWN FIRE REVIEW Approved
02/01/2013 RONALD BROWN ADA REVIEW Passed
02/14/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Toilets are not accessible.
2. Show store front doors and sidelights at both ends of building.
3. Min interior door clearance for accessibility to be 32".
4. Break Room sink to be 2'-10" a.f.f.
5. Provide 48" clear between double doors from the end of the opend edge of the first door to the wall of the second door.
END OF REVIEW.
02/20/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
02/20/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the mechanical design as required to avoid using the corridor as a return air duct. Reference: Section 601.2, IMC 2006
02/20/2013 CPIERCE1 WWM REVIEW Needs Review
02/20/2013 ROBERT SHERRY WATER REVIEW Approved
02/27/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11CM03155

1. Mecanical Plans show units HP 1,2 and 3 as new, Electrical Plans indicate existing.
2. Plumbing Plans show 3 instantaneous water heaters at 208 volt 2.6kw, 14.6 amps, the Electrical plans show 2 water heaters on single 20 amp circuit.
3. Panel A shown as being existing, where do all other circuits go which are not marked for this project in Panel A go?
4. Circuit A-31 in panel schedule, va load incorrect.

Ray T Majuta
Elect Plan Review
PDSD, Tucson
2/27/2013
Ray.Majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
03/01/2013 CPIERCE1 REJECT SHELF Completed