Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T11CM03155
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/01/2013 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 02/01/2013 | RONALD BROWN | ADA | REVIEW | Passed | |
| 02/14/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Toilets are not accessible. 2. Show store front doors and sidelights at both ends of building. 3. Min interior door clearance for accessibility to be 32". 4. Break Room sink to be 2'-10" a.f.f. 5. Provide 48" clear between double doors from the end of the opend edge of the first door to the wall of the second door. END OF REVIEW. |
| 02/20/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 02/20/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the mechanical design as required to avoid using the corridor as a return air duct. Reference: Section 601.2, IMC 2006 |
| 02/20/2013 | CPIERCE1 | WWM | REVIEW | Needs Review | |
| 02/20/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 02/27/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T11CM03155 1. Mecanical Plans show units HP 1,2 and 3 as new, Electrical Plans indicate existing. 2. Plumbing Plans show 3 instantaneous water heaters at 208 volt 2.6kw, 14.6 amps, the Electrical plans show 2 water heaters on single 20 amp circuit. 3. Panel A shown as being existing, where do all other circuits go which are not marked for this project in Panel A go? 4. Circuit A-31 in panel schedule, va load incorrect. Ray T Majuta Elect Plan Review PDSD, Tucson 2/27/2013 Ray.Majuta@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/01/2013 | CPIERCE1 | REJECT SHELF | Completed |