Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T11CM03136
Parcel: 14042002A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM03136
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/29/2011 TERRY STEVENS ZONING REVIEW Approved
09/29/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
09/29/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Needs Review Provide 2006 IECC Budget Lighting Calculations for review,
Submit plans for review, too large for walk thur.

Ray Majuta
Elect Plan Review
PDSD, City of Tucson
9/29/11
Ray.majuta@tucsonaz.gov
09/29/2011 ROBERT SHERRY WATER REVIEW Approved
09/29/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. The newly added most Southerly located exterior door at the larger training room requires panic hardware.
SHEET A2
2. Detail 4A/2:
a. Does not work for lavatory section in detail 1/A2, does not comply with ICC/ANSI 117.1, Sections 6-6.1, 305.3 and 306. Please provide a vanity/lavatory section showing accessible compliance.
3. Detail 1/A2:
a. Please show all required accessible requirements on the toilet floor plan plan. Please include all accessories, dimensions, clearances, fixtures required and toilet elevation references.
4. Please provide large scale toilet elevations showing all required accessibility requirements. Please include all accessories, dimensions, clearances and fixtures required.
5. Please provide structural calculations and details for all new and or replaced roof top mounted HVAC equipment.
6. Please provide structural calculations and details for the suspended water heater.
END OF REVIEW
09/29/2011 JASON GREEN ENGINEERING REVIEW Approved
09/29/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. No more than one trap shall be installed on a trap arm (see the sink located in the lounge). Reference: Section 1001.1, UPC 2006.
2. Clarify the size of the water heater, it is called out as a 20-gallon unit on P1 but scheduled as a 66-gallon on P2.
3. The maximum length of the horizontal section of a vent may not exceed one-third of the total allowable vent length noted in Table 7-5, UPC 2006 (see the vent for the mop sink; a 1-1/2" vent has a maximum horizontal length of 20 feet).
09/29/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/29/2011 RONALD BROWN ADA REVIEW Passed
09/30/2011 GERRY KOZIOL WWM REVIEW Approved
09/30/2011 MARTIN BROWN FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/05/2011 CPIERCE1 REJECT SHELF Completed