Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM03136
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/29/2011 | TERRY STEVENS | ZONING | REVIEW | Approved | |
09/29/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
09/29/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | Provide 2006 IECC Budget Lighting Calculations for review, Submit plans for review, too large for walk thur. Ray Majuta Elect Plan Review PDSD, City of Tucson 9/29/11 Ray.majuta@tucsonaz.gov |
09/29/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
09/29/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. The newly added most Southerly located exterior door at the larger training room requires panic hardware. SHEET A2 2. Detail 4A/2: a. Does not work for lavatory section in detail 1/A2, does not comply with ICC/ANSI 117.1, Sections 6-6.1, 305.3 and 306. Please provide a vanity/lavatory section showing accessible compliance. 3. Detail 1/A2: a. Please show all required accessible requirements on the toilet floor plan plan. Please include all accessories, dimensions, clearances, fixtures required and toilet elevation references. 4. Please provide large scale toilet elevations showing all required accessibility requirements. Please include all accessories, dimensions, clearances and fixtures required. 5. Please provide structural calculations and details for all new and or replaced roof top mounted HVAC equipment. 6. Please provide structural calculations and details for the suspended water heater. END OF REVIEW |
09/29/2011 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
09/29/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. No more than one trap shall be installed on a trap arm (see the sink located in the lounge). Reference: Section 1001.1, UPC 2006. 2. Clarify the size of the water heater, it is called out as a 20-gallon unit on P1 but scheduled as a 66-gallon on P2. 3. The maximum length of the horizontal section of a vent may not exceed one-third of the total allowable vent length noted in Table 7-5, UPC 2006 (see the vent for the mop sink; a 1-1/2" vent has a maximum horizontal length of 20 feet). |
09/29/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
09/29/2011 | RONALD BROWN | ADA | REVIEW | Passed | |
09/30/2011 | GERRY KOZIOL | WWM | REVIEW | Approved | |
09/30/2011 | MARTIN BROWN | FIRE | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
10/05/2011 | CPIERCE1 | REJECT SHELF | Completed |