Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM03133
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/29/2011 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 09/29/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide information on the sequence of operation for the restroom exhaust fans to show that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2006. 2. Provide calculations demonstrating adequate ventilation. (Note that a balance report will be required at the conclusion of the activity.) Reference: Section 403.3, IMC 2006, as amended by the City of Tucson. |
| 09/29/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Need to comply with Mechanical Plan Examiner's requirement to interconnect ex-fan in resroom to air coming into space. Ray T Majuta 9/29/11 |
| 09/29/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 09/29/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 09/29/2011 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 09/29/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 09/29/2011 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 09/29/2011 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 09/29/2011 | RONALD BROWN | ADA | REVIEW | Passed | |
| 09/29/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/29/2011 | DELMA ROBEY | OUT TO CUSTOMER | Completed |