Review Date Reviewer's Name Type of Review Description Status Comments
09/29/2011 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2005 National Electrical Code and Arizona Revised Statutes. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
All corrections and revisions shall be made on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets. (Do not cloud the changes made for comment revisions). Incorporate changes on originals and provide two copied sets for review.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

GENERAL NOTES:
1. Provide legible notation (minimum 3/32" lettering), sheet #05.
2. Provide manufacturer specification sheets for the mounting hardware.
3. The manufacturer's maximum recommended inverter input PV-Power is 4820W. Show an inverter with an input rating consistent with total photovoltaic output capacity of 5060W. The 2005 NEC does not recognize de-rating measures for UL tested and certified equipment. Please provide an Arizona registrant analysis for an appeal to the City of Tucson Building Official if pursuing approval for an underrated inverter.
4. Clarify the wattage rating of the (23) modules shown on sheet #02.
5. Clarify the total number of modules at the single string array shown on sheet #05.