Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T11CM03081
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/29/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
11/29/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
11/29/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | The resubmitted energy calculations are for the Town of Pima, Arizona, located in Graham County Arizona. Provide calculations based on Pima County < 4,000 Feet. No details were submitted concerning the R-27.6 continuous insulation. Based on the wall sections shown on sheet A3.0, there are four types of walls but only one wall type is shown in the calculations. [Second comment: The submitted calculations are for Green Valley, Arizona, not Pima County < 4,000 feet. Provide details for the continuous insulation R-value of 27.6.] [Original comment: Provide energy code compliance calculations for the additions to the building envelope; use the climate zone for Pima County < 4,000 feet. Provide sufficient detail on the drawings to evaluate the energy compliance of the additions to the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections 101.4, 101.4.3, and 104.2, International Energy Conservation Code 2006.] |
12/01/2011 | CAGUILA1 | ENGINEERING | REVIEW | Needs Review | |
12/01/2011 | CAGUILA1 | ZONING | REVIEW | Needs Review |