Permit Number: T11CM03081
Parcel: 13331159T

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM03081
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/21/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/22/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied The submitted calculations are for Green Valley, Arizona, not Pima County < 4,000 feet. Provide details for the continuous insulation R-value of 27.6. [Original comment: Provide energy code compliance calculations for the additions to the building envelope; use the climate zone for Pima County < 4,000 feet. Provide sufficient detail on the drawings to evaluate the energy compliance of the additions to the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections 101.4, 101.4.3, and 104.2, International Energy Conservation Code 2006.]
11/22/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not resolved; show the location and size for each water hammer arrestor. [Original comment: Show size, location, and model number of hammer arrestors to be installed on the cold water system. Reference: Section 604.9, 2006 IPC.]
2. Comment not resolved; the revised drawing now shows one of the drains labeled as both sanitary and grease waste. [Original comment: Clarify waste and vent piping isometric on sheet P-1.0 which drain is "san" and which is "grease waste".]
3. Coordinate the waste and vent diagram with the plumbing plan. [Original comment: Show how the horizontally wet vented fixtures for the two bathrooms, qualifies as a "bathroom group". Reference: chapter two, definition of "bathroom group". Reference 909.1 2006 IPC; horizontal wet vent permitted. Any combination of fixtures within two bathroom groups.... and a bathroom group is defined as a water closet, lavatory, bathtub or shower, including or excluding a bidet, an emergency floor drain or both. Waste and vent piping plan on sheet P1.0 shows three water closets and a urinal.]
11/29/2011 CAGUILA1 ENGINEERING REVIEW Needs Review
11/29/2011 CAGUILA1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
11/29/2011 CAGUILA1 ZONING REVIEW Needs Review