Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T11CM03081
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/15/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PREVIOUS COMMENTS; SHEETS 3.2 AND S4.0: CALCULATIONS WERE NOT PROVIDED FOR THE SUPPORT/CONNECTION OF THE NEW SIGN. PROVIDE. 2. PREVIOUS COMMENT; SHEET CV (BUILDING CODE): REVISE THE ACCESSIBILITY CODE TO THE ICC/ANSI A117.1-2003. 3. PREVIOUS COMMENT; SHEET A1.1 (ROOF PLAN): SHOW THE EXISTING ROOF SLOPES AND DRAIN SYSTEM ALONG WITH THE LOCATION OF THE HVAC UNITS AND NEW ROOF WALKWAYS AS SPECIFIED IN NOTE 3. 4. PREVIOUS COMMENT: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 11/21/2011 | CAGUILA1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
| 11/21/2011 | CAGUILA1 | ZONING | REVIEW | Needs Review | |
| 11/21/2011 | CAGUILA1 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
| 11/21/2011 | CAGUILA1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 11/21/2011 | CAGUILA1 | ENGINEERING | REVIEW | Needs Review |