Permit Review Detail
Review Status: Completed
Review Details: SITE
Permit Number - T11CM03078
Review Name: SITE
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/26/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
| 09/26/2011 | RONALD BROWN | H/C SITE | REVIEW | Passed | COT OWNED PROPERTY REF ADA FOLDER FOR REVIEW COMMENTS |
| 10/03/2011 | STEVE SHIELDS | ZONING | REVIEW | Passed | |
| 10/03/2011 | RBROWN1 | ADA | REVIEW | Denied | 1. Please provide accessible seating for all fixed seating areas as required by ADAAG 1994 Edition, Section 4.1.3 (18). 2. Please indicate on the drawings that the slopes of all accessible routes comply with ADAAG 1994 Edition, Section 4.3.7. 3. At detail 8/D-1, please indicate on the drawings that the gate hardware height complies with ADAAG 1994 Edition, Section 4.13.9. END OF REVIEW |
| 10/05/2011 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | The site plan is approved. No grading permit will be required in accordance with Development Standard 11-01.2.2.A and because no SWPPP is required as the disturbed area is less than one acre. |
| 10/20/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the site drawing to include the location and size of the potable water meter and of the backflow prevention assembly. Reference: City of Tucson Development Standard No. 2-05.0, Section 2.3 D and Section 103.2.3, UPC 2006. 2. Sheet SP-1 shows an existing ¾" potable water line being extended to serve two new drinking fountains. Detail 1/D-1 shows a 1" potable water line serving each drinking fountain; coordinate the drawings. Reference: Section 103.2.3, UPC 2006. 3. The specified drinking fountain, Haws 3500, requires a minimum flowing water pressure of 30 PSI for proper operation. Provide water pressure and water pipe sizing calculations. Reference: Section 610.1, UPC 2006. 4. Provide the model number of the proposed backflow preventer for the drinking fountains (detail 1/D-2). Reference: Section 103.2.3, UPC 2006. |
| 10/21/2011 | ANDREW CONNOR | LANDSCAPE | REVIEW | Approved | |
| 10/21/2011 | ANDREW CONNOR | NPPO | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/24/2011 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 10/24/2011 | SUE REEVES | REJECT SHELF | Completed |