Permit Number: T11CM03071
Parcel: 10709025A

Address:
2525 N ORACLE RD

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T11CM03071
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/23/2011 PAUL MACHADO ENGINEERING REVIEW Approved
10/14/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/14/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
10/28/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved 1) Provide available ground fault information for new panel A and existing panel B

2) Provide correct panel schedule showing panel B being fed from panel A

3) Provide conductor and conduit sizes

4) Show routing of conduits in parking lot
10/28/2011 DAVID RIVERA ZONING REVIEW Approved
10/28/2011 MARTIN BROWN FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/02/2011 GERARDO BONILLA OUT TO CUSTOMER Completed