Permit Number: T11CM03062
Parcel: 131132580

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM03062
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/05/2011 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
12/06/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
12/19/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The specified accessible water closet (WCHC) requires a minimum operating pressure of 20 PSI; revise the water pressure calculations as required. [Initial comment: The architectural plans specify the installation of a pressure-assisted water closet. Revise the water pressure calculations as required to account for the minimum water pressure requirement of the specified water closet. Reference: Section 608.1, UPC 2006.]
2. Provide material standards for all plumbing fixtures being provided by others. Reference: Section 401.1, UPC 2006.
3. Provide information from the PEX manufacturer that allows 200 PPM chlorine to be used for sterilization of the PEX tubing. [Initial comment: Specify how sterilization of the domestic water piping (e.g. PEX) will be accomplished per Section 609.9, UPC 2006.]
4. Fixtures located on floor levels more than 12" above the rim elevation of the next upstream manhole or cleanout shall not drain through the backwater valve. Reference: Section 710.1, UPC 2006, as amended by the City of Tucson. [Initial comment: Provide the rim elevation of the next upstream sanitary manhole or cleanout and the first floor elevation of the apartment building. Determine the need for a backwater valve per Section 710.1, UPC 2006, as amended by the City of Tucson.]
12/22/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the submitted flue calculations per Section 504, IFGC 2006. [Initial comment: Provide the total flue heights for both installation types (74.MBH and 96 MBH) on both floors. Show that the flue sizes meet the requirements of Section 504.3, IFGC 2006.]