Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T11CM03062
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/05/2011 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 12/06/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/19/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The specified accessible water closet (WCHC) requires a minimum operating pressure of 20 PSI; revise the water pressure calculations as required. [Initial comment: The architectural plans specify the installation of a pressure-assisted water closet. Revise the water pressure calculations as required to account for the minimum water pressure requirement of the specified water closet. Reference: Section 608.1, UPC 2006.] 2. Provide material standards for all plumbing fixtures being provided by others. Reference: Section 401.1, UPC 2006. 3. Provide information from the PEX manufacturer that allows 200 PPM chlorine to be used for sterilization of the PEX tubing. [Initial comment: Specify how sterilization of the domestic water piping (e.g. PEX) will be accomplished per Section 609.9, UPC 2006.] 4. Fixtures located on floor levels more than 12" above the rim elevation of the next upstream manhole or cleanout shall not drain through the backwater valve. Reference: Section 710.1, UPC 2006, as amended by the City of Tucson. [Initial comment: Provide the rim elevation of the next upstream sanitary manhole or cleanout and the first floor elevation of the apartment building. Determine the need for a backwater valve per Section 710.1, UPC 2006, as amended by the City of Tucson.] |
| 12/22/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the submitted flue calculations per Section 504, IFGC 2006. [Initial comment: Provide the total flue heights for both installation types (74.MBH and 96 MBH) on both floors. Show that the flue sizes meet the requirements of Section 504.3, IFGC 2006.] |