Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T11CM03062
Parcel: 131132580

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM03062
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/23/2011 MARTIN BROWN FIRE REVIEW Approved
09/29/2011 JASON GREEN ENGINEERING REVIEW Approved
09/30/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approv-Cond 1. SHEET A-1: The accessibility statemenmt that section 1107.62 of the 20056 IBC is revelant for Type "A" accessible units is superceeded by Section 1103.2.2, Existing Buildings. Reference Section 3909.1, Scope plus Exception. No accessible units are required for existing buildings.
a. If so desired, the accessible unit Type "A" for unit #4 in building 6141 may remain but is not required.
2. Please provide special inspection Certifications for approval.
END OF REVIEW
10/07/2011 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Denied Plan review completed by Dan Santa-Cruz. Please call 909-5173 for questions or comments.

1) PP E-801 service "A" is showing 150A disconnects for typical apt panels. Typical panels are only 100A, please reconcile

2) PP E-901 Service "C" & "D" missing information for breaker sizes

3) PP E-801 notation #2 is insufficient for plan approval. Please provide available fault current information for services and sub-panels.

4) Light fixture type "0" inside units has not been specified. Please provide information.

5) Provide IECC compliance certificate.
10/14/2011 ROBERT SHERRY WATER REVIEW Passed
10/17/2011 STEVE SHIELDS ZONING REVIEW Approved
10/17/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Clarify the natural gas input to furnace types FUR-1 and FUR-2; the mechanical schedule indicates 44 MBH but the plumbing schedule shows 44.5 MBH. Reference: Section 106.3.1, IMC 2006.
2. Show how the design of the cooling coils complies with Section 307.2.3 IMC 2006 with respect to secondary drain systems for the condensate.
3. Verify that the doors for the clothes dryer locations comply with Section 504.5, IMC 2006 for make-up air.
4. Provide access for the condensate drain terminating with a direct connection to a bathtub overflow. Reference: Section 807.2, UPC 2006.
5. Provide clarification of the gas flues for the water heaters and furnaces. The keynotes (i.e. #2 and #21) on sheet M101 appear to relate only to the common flues from the first floor up to the second floor and not from the second floor to the roof. Reference: Section 106.3.1, IFGC 2006.
6. Provide the total flue heights for both installation types (74.MBH and 96 MBH) on both floors. Show that the flue sizes meet the requirements of Section 504.3, IFGC 2006.
10/17/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The architectural plans specify the installation of a pressure-assisted water closet. Revise the water pressure calculations as required to account for the minimum water pressure requirement of the specified water closet. Reference: Section 608.1, UPC 2006.
2. Specify how sterilization of the domestic water piping (e.g. PEX) will be accomplished per Section 609.9, UPC 2006.
3. Provide pressure-absorbing devices for the water connections to appliances equipped with quick-acting or solenoid valves. Reference: Section 609.10, UPC 2006.
4. Verify the sizes of the PEX water distribution lines, as shown on the drawings, will not result in pressure drops greater than indicated in the water pressure calculations. Reference: Section A 5, UPC 2006.
5. Provide the rim elevation of the next upstream sanitary manhole or cleanout and the first floor elevation of the apartment building. Determine the need for a backwater valve per Section 710.1, UPC 2006, as amended by the City of Tucson.
6. Revise the gas piping sizes for apartment numbers 3, 8, 9, and 10; based on the mechanical design, these apartments have a total gas demand of 179 MBH, not 157 MBH. Reference: Section 1217.3, UPC 2006 and Section 402, IFGC 2006.
7. Verify the total gas demand for the apartments equipped with furnaces FUR-1 or FUR-2. If the units do have an input of 44.5 MBH, the main gas pipe is undersized. Reference: Section 1217.3, UPC 2006 and Section 402, IFGC 2006.
10/25/2011 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/02/2011 SUE REEVES OUT TO CUSTOMER Completed
12/02/2011 SUE REEVES REJECT SHELF Completed