Review Details: PLANS OK TO SUBMIT - COMM
Permit Number - T11CM03056
Review Name: PLANS OK TO SUBMIT - COMM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/22/2011 | MICHAEL ST. PAUL | ZONING | REVIEW | Passed | |
| 09/22/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 09/22/2011 | CPIERCE1 | FIRE | REVIEW | Needs Review | |
| 09/22/2011 | RBROWN1 | ADA | REVIEW | Passed | |
| 09/22/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Please provide structural analysis of the exiting shade structure for the newly added laod of the PV system. Insure bracket attachments are also analyized. 2. Please finish section AA/295A as to Support Triangle detail on sheet 295B. END OF REVIEW |
| 09/22/2011 | JASON GREEN | ENGINEERING | REVIEW | Approved |