Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM03053
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/19/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PREVIOUS COMMENT: GENERAL: PROVIDE STRUCTURAL NOTES ON THE DRAWINGS FOR MATERIALS, LOADINGS, FOUNDATIONS, ETC. 2. PREVIOUS COMMENT: GENERAL: PROVIDE ARCHITECTURAL SPECIFICATIONS AS REQUIRED. |
| 10/19/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Revise the size of the primary and overflow scuppers to comply with the requirements of Section 1101.11.2.1, UPC 2006 (minimum size 6.3" wide x4" high). |
| 10/19/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Comment not resolved. The U-factors and the SHGC for the glazing does not meet the requirements of the prescriptive values (section 502, IECC 2006) and while the drawing calls out 1/4" glazing, the U-Factor chart refers to 1" glazing. Provide energy code compliance calculations or show that the addition complieswith the prescriptive requirements. [Original comment: Provide energy code compliance calculations for the building envelope; use the climate zone for Pima County < 4,000 feet. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006.] 2. Comment not addressed. Provide structural calculations to verify that the roof is capable of supporting the roof top unit. Reference: Section 302.1, IMC 2006. |
| 10/20/2011 | CPIERCE1 | WWM | REVIEW | Needs Review | |
| 10/20/2011 | CPIERCE1 | ZONING | REVIEW | Needs Review | |
| 10/20/2011 | CPIERCE1 | FIRE | REVIEW | Needs Review | |
| 10/20/2011 | CPIERCE1 | ENGINEERING | REVIEW | Needs Review |