Permit Number: T11CM03052
Parcel: 11713037A

Address:
50 E BROADWAY BL

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM03052
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/07/2012 MARTIN BROWN FIRE REVIEW Approved
03/08/2012 RONALD BROWN ADA REVIEW Passed
03/15/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied SHEET A1.1
1. Please show the existing exit stairs.
2. Move the westerly exit ramp and door to the north for exit clearance of the toilet room door.
3. Insure tha the ladder to the roof does not intrude into the accessible route more tha 4" as required by ICC A117.1, Section 307.
SHEET A3.0
4. Ditto Comments 1 and 2 above.
5. It appears as the toiles are being shared with the southerly tenant. Please provide occupant load and toilet fixture calculations for both spaces sharing tyhese two toilets.
6. Please provide a large scale detail of the new ramp showing all accessible requirements as dimensions, elevations, handrails, landings and clearances.
a. Please provide a complete handrail elevation.
7. Please provide health department activity number.
8. Insure panic hardare on door 104a and the additional two existing exit doors.
9. Please provide structural calculations and details for the exhaust hood support.
SHEET A9.0
10. Please finish the handrails at detail 9.
SHEET M1.1
11. Please provide structural calculations for all new roof top mounted HVAC equipment.
END OF REPORT
03/19/2012 ROBERT SHERRY WATER REVIEW Denied Provide the size of the existing water meter and the total connected water demand that will result from the addition of this activity. Reference: Sections 610.1 and 610.2, UPC 2006.
03/19/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify the plumbing code to be used for this activity. The Plumbing Specifications on sheet P9.1 refer to the 2006 UPC but the Code analysis on sheet a1.0 refers to both the 2006 IPC and the 2006 UPC. This review has been made using the 2006 UPC.
2. The specified hydromechanical grease interceptor has a 4" outlet but the downstream pipe is only 3". Any fitting or connection in a drainage system that results in a reduction of the pipe area is prohibited. Reference: Section 316.4.1, UPC 2006.
3. Verify that adequate maintenance space for the hydromechanical grease interceptor is available considering the installation of gas meter and the reduced pressure backflow preventer in the same small area. Reference: Section 1009.5, UPC 2006.
03/19/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide structural calculations and details to show that the Type I hood is supported from the building structure in accordance with Section 507.6, IMC 2006. Reference: Section 302.1, IMC 2006.
2. Clarify the construction of the wall behind the Type I hood - keynote 31 on sheet a3.0 refers to it as a pony wall. Verify that the listing of the hood allows for it to be used as an island canopy with the same exhaust flow.
3. The mechanical plan shows the installation of a 4-way ceiling diffuser within four feet of the Type I hood. Verify that the hood listing will allow this application. Reference: Section 507.1 exception (1), IMC 2006.
03/22/2012 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
04/04/2012 GERRY KOZIOL WWM REVIEW Approved