Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T11CM03045
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/27/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
11/01/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
11/04/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Comment not addressed. The drawing shows a total exhaust rate of 1250 CFM from the rooms served by A/C units AC-5.1 and AC-5.2 with a total flow of only 600 CFM of outside air through the two A/C units. Show how the rooms are maintained at a positive pressure compared to the repair garage. Reference: Section 404.3, IMC 2006. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
11/29/2011 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |
11/29/2011 | SUE REEVES | REJECT SHELF | Completed |