Permit Number: T11CM03045
Parcel: 13216600A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM03045
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/27/2011 DAVE MANN FIRE REVIEW Approved
11/01/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
11/04/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not addressed. The drawing shows a total exhaust rate of 1250 CFM from the rooms served by A/C units AC-5.1 and AC-5.2 with a total flow of only 600 CFM of outside air through the two A/C units. Show how the rooms are maintained at a positive pressure compared to the repair garage. Reference: Section 404.3, IMC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/29/2011 GERARDO BONILLA OUT TO CUSTOMER Completed
11/29/2011 SUE REEVES REJECT SHELF Completed