Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T11CM03045
Parcel: 13216600A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM03045
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/21/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of the roof top units. Reference: Section 302.1, IMC 2006.
2. Clarify keynotes 29, 30, and 31 on sheet M4.2; they are used on the drawing. Reference: Section 106.3.1, IMC 2006.
3. Provide the size of the cooler drain pipe between EC-5.2 and EC-5.3. Reference: Section 106.3.1, IMC 2006.
4. The drawing shows a total exhaust rate of 1250 CFM from the rooms served by A/C units AC-5.1 and AC-.2 with a total flow of only 600 CFM of outside air through the two A/C units. Show how the rooms are maintained at a positive pressure compared to the repair garage. Reference: Section 404.3, IMC 2006.
09/21/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
09/22/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
09/28/2011 CPIERCE1 BUILDING-COMMERCIAL REVIEW Needs Review
09/28/2011 CPIERCE1 FIRE REVIEW Needs Review