Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM03045
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/21/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
09/21/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of the roof top units. Reference: Section 302.1, IMC 2006. 2. Clarify keynotes 29, 30, and 31 on sheet M4.2; they are used on the drawing. Reference: Section 106.3.1, IMC 2006. 3. Provide the size of the cooler drain pipe between EC-5.2 and EC-5.3. Reference: Section 106.3.1, IMC 2006. 4. The drawing shows a total exhaust rate of 1250 CFM from the rooms served by A/C units AC-5.1 and AC-.2 with a total flow of only 600 CFM of outside air through the two A/C units. Show how the rooms are maintained at a positive pressure compared to the repair garage. Reference: Section 404.3, IMC 2006. |
09/22/2011 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
09/28/2011 | CPIERCE1 | FIRE | REVIEW | Needs Review | |
09/28/2011 | CPIERCE1 | BUILDING-COMMERCIAL | REVIEW | Needs Review |