Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM03044
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/21/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
09/21/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Describe the operations being conducted in building 3 and how the ventilation exhaust flow rate was determined. Reference: Section 106.3.1, IMC 2006. 2. Show how the discharge duct for EF-3.1 is to be supported. Reference: Section 301.12, IMC 2006. 3. Show how the exhaust discharge outlet for EF-3.1 complies with Section 501.2, IMC 2006. |
09/22/2011 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
09/28/2011 | CPIERCE1 | FIRE | REVIEW | Needs Review | |
09/28/2011 | CPIERCE1 | BUILDING-COMMERCIAL | REVIEW | Needs Review |