Permit Number: T11CM03044
Parcel: 13216600A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM03044
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/21/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
09/21/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Describe the operations being conducted in building 3 and how the ventilation exhaust flow rate was determined. Reference: Section 106.3.1, IMC 2006.
2. Show how the discharge duct for EF-3.1 is to be supported. Reference: Section 301.12, IMC 2006.
3. Show how the exhaust discharge outlet for EF-3.1 complies with Section 501.2, IMC 2006.
09/22/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
09/28/2011 CPIERCE1 FIRE REVIEW Needs Review
09/28/2011 CPIERCE1 BUILDING-COMMERCIAL REVIEW Needs Review