Permit Number: T11CM03041
Parcel: 13506136E

Address:
2550 S KOLB RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM03041
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/09/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
01/09/2012 ROBERT SHERRY WATER REVIEW Approved
01/12/2012 GERRY KOZIOL WWM REVIEW Denied NEED TO SHOW LOCATION/METHOD OF CONNECTION TO PUBLIC SEWER.
NEED PCRWRD REIVEW OF LOCATION/METHOD OF CONNECTION TO PUBLIC SEWER - CHAD AMATEAU- 740-6647
NEED PCRWRD 3RD FLOOR CAPACITY REVIEW - KURT STEMM 740-6200
NEED IWC REVIEW & APPROVAL OF GREASE INTERCEPTOR - TOM TOMCHAK - 5025 W INA RD - 442-6200
1. WALMART - SITE PLAN WITH 6" PRIVATE SEWER EXITING BLDG

2. NEED PCRWRD REVIEW OF LOCATION/ METHOD OF CONNECTION TO PUBLIC SEWER - CHAD AMATEAU - 740-6647 UTILITY PLAIN C8.2 - NEED COPY OF PVT SEWER FOR BASE MAP - NEED DEQ APPROVAL IF MULTIPLE BLDGS

3.NEED PCRWRD 3RD FLOOR CAPCITY REVIEW - KURT STEMM - 740-6607

4. NEED WASTEWATER INDUSTRIAL CONTROL (IWC) REVIEW & APPROVAL OF GREASE INTERCEPTOR - TOM TOMCHAK - 5025 W INA RD - 443-6200

5. NEED TO SUBMIT DEMO DRAWINGS SHOWING ALL WASTERWATER PLUMBING FIXTURES REMOVED FOR WASTEWATER CONNECTIO FEE CREDIT - NEED 5TH FLOOR MAPS & RECORDS CREDIT EVALUATION - 740-6602

6. NEED MANHOLE TAP PERMIT APPROVAL YVONNE 740-6733
12/27/2011 DAVE MANN FIRE REVIEW Denied Fire Comments:

Provide written reponses to comments including where corrections are located on the plans.

The 4th exit through the stockroom requires a "demarcated, minimum 44-inch-wide aisle defined by full or partial fixed wall or similar construction that will maintain the required width and lead directly from the retail area to the exit without obstructions." Refer to 2006 IFC, 1014.2, exception 2.4.
12/29/2011 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Walmart @Kolb & Golf Links
T11CM03041
Building Plan (2nd Review)

TRANSMITTAL DATE: December 12, 2011

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning has reviewed the submitted building plans and it appears that the proposed building plans match the approved site plans. Due to the number of comments by other agencies Zoning will not stamp and approve the plans until the next submittal.

3. Zoning is willing to provide an over-the-counter review once all other agencies have approved. Call or email to schedule the over-the-counter review.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956