Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T11CM03041
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/16/2011 | DAVE MANN | FIRE | REVIEW | Denied | The 4th exit through the stockroom requires a "demarcated, minimum 44-inch-wide aisle defined by full or partial fixed wall or similar construction that will maintain the required width and lead directly from the retail area to the exit without obstructions." Refer to 2006 IFC, 1014.2, exception 2.4. |
| 11/16/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PREVIOUS COMMENT 3: PROVIDE THE REVISED PLANS AND STRUCTURAL CALCULATIONS FOR THE LIGHT POLE FOUNDATION IN THE NEXT SUBMITTAL. 2. PREVIOUS COMMENT 9: THE LETTER OF REQUEST FOR THE DEFERRED SUBMITTALS WAS NOT LOCATED IN THIS SUBMITTAL. PROVIDE. 3. SHEET SP2.1; SCREENING PLAN 7: SECTIONS 9-SP2.1 AND 5-SP2.1 INDICATED ON THE PLAN ARE NOT ON SHEET SP2.1. CLARIFY (REFER TO SHEET S2.2?). 4. SHEET SP2.1; ELEVATION 8B: SECTION 12-SP2.1 INDICATED ON THE ELEVATION IS NOT ON SHEET SP2.1. CLARIFY (REFER TO SHEET S2.2?). 5. PREVIOUS COMMENT 13: PROVIDE THE APPROVED SITE DEVELOPMENT PLAN WITH THE NEXT SUBMITTAL. 6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 11/17/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 11/17/2011 | ROBERT SHERRY | WATER | REVIEW | Denied | Comment not resolved; the location of the 2" water meter and the 3" reduced pressure zone backflow preventer is not shown on civil sheet C4.0. [Original comment: Provide the size of the water meter and the size of the reduced pressure backflow preventer serving this building. Reference: Section 106.3.1, IPC 2006.] |
| 11/17/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 11/21/2011 | GERRY KOZIOL | WWM | REVIEW | Denied | NEED TO SHOW LOCATION/METHOD OF CONNECTION TO PUBLIC SEWER. NEED PCRWRD REIVEW OF LOCATION/METHOD OF CONNECTION TO PUBLIC SEWER - CHAD AMATEAU- 740-6647 NEED PCRWRD 3RD FLOOR CAPACITY REVIEW - KURT STEMM 740-6200 NEED IWC REVIEW & APPROVAL OF GREASE INTERCEPTOR - TOM TOMCHAK - 5025 W INA RD - 442-6200 NEED TO SUBMIT DEMO DRAWINGS SHOWING ALL WASTERWATER PLUMBING FIXTURES REMOVED FOR WASTEWATER CONNECTIO FEE CREDIT - NEED 5TH FLOOR MAPS & RECORDS CREDIT EVALUATION - 740-6602 |
| 11/29/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 12/12/2011 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 12/12/2011 | STEVE SHIELDS | ZONING | REVIEW | Denied | PDSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: Walmart @Kolb & Golf Links T11CM03041 Building Plan (2nd Review) TRANSMITTAL DATE: December 12, 2011 1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. Zoning has reviewed the submitted building plans and it appears that the proposed building plans match the approved site plans. Due to the number of comments by other agencies Zoning will not stamp and approve the plans until the next submittal. 3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved site plan. Additional comments may be forthcoming. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/13/2011 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 12/13/2011 | DELMA ROBEY | REJECT SHELF | Completed |