Permit Number: T11CM03028
Parcel: 12108093A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM03028
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/17/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11CM03028, 6280 E Pima,#110, Tuc,AZ
Medical Offices

1. The Plumbing Plan shows a 4500 Watt electrical water heater at 208v/3p/60, not listed on power plan or panel schedule ?
2.Sheet E-5 shows an existing 200 amp fused disconnect going to a j-box then splitting to feed panels D and DA with
two sets of 4 # 1 thwn's, #8 grd for each panel, Panel D is a main lugs only 200 a pnl ? No protection on #1 feeders ?

Ray Majuta
Elect Pln Ck
PDSD,COT
10/15/11