Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T11CM03028
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/17/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T11CM03028, 6280 E Pima,#110, Tuc,AZ Medical Offices 1. The Plumbing Plan shows a 4500 Watt electrical water heater at 208v/3p/60, not listed on power plan or panel schedule ? 2.Sheet E-5 shows an existing 200 amp fused disconnect going to a j-box then splitting to feed panels D and DA with two sets of 4 # 1 thwn's, #8 grd for each panel, Panel D is a main lugs only 200 a pnl ? No protection on #1 feeders ? Ray Majuta Elect Pln Ck PDSD,COT 10/15/11 Ray.majuta@tucsonaz.gov |