Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM03028
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/19/2011 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 09/21/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Coordinate the ductwork design with the architect to accomodate the required fire-rated egress corridor. |
| 09/21/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 09/21/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 09/21/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A1.0; FLOOR PLAN: ALL CORRIDOR WALLS MUST MEET THE FIRE RESISTANCE RATING LISTED IN THE 2006 IBC, TABLE 1017.1. ADD DETAIL FOR THIS WALL CONSTRUCTION. 2. SHEET A1.0; FLOOR PLAN: ALL CORRIDOR DOORS MUST MEET THE FIRE RESISTANCE RATING LISTED IN THE 2006 IBC, TABLE 715.4. REVISE THE SCHEDULE ON SHEET A4.0. 3. SHEET A1.0; FLOOR PLAN: PROVIDE A HIGH/LOW DRINKING FOUNTAIN OR SINGLE POINT-OF-USE WATER DISPENSER PER THE 2006 IBC, TABLE 2902.1. 4. SHEET A3.1; ROLL IN SHOWER: A ROLL IN SHOWER REQUIRES GRAB BARS PER THE ICC/ANSI A117.1-2003, SECTION 608.2.2. REVISE THE ELEVATION ON THIS SHEET. 5. SHEET A1.0: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE KEYNOTES. 6. SHEET P2.0; WATER HEATER DETAIL: INCLUDE IN THIS DETAIL HOW THE WATER HEATER IS SUPPORTED, INCLUDING FRAMING MEMBER SIZES AND HOW THEY ARE CONNECTED TO THE STUD WALL. |
| 09/21/2011 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 09/21/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 09/21/2011 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 09/21/2011 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 09/21/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 10/06/2011 | DROBEY1 | WWM | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/06/2011 | DELMA ROBEY | OUT TO CUSTOMER | Completed |