Permit Number: T11CM03028
Parcel: 12108093A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM03028
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/19/2011 MICHAEL ST. PAUL ZONING REVIEW Approved
09/21/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Coordinate the ductwork design with the architect to accomodate the required fire-rated egress corridor.
09/21/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Needs Review
09/21/2011 ROBERT SHERRY WATER REVIEW Approved
09/21/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A1.0; FLOOR PLAN: ALL CORRIDOR WALLS MUST MEET THE FIRE RESISTANCE RATING LISTED IN THE 2006 IBC, TABLE 1017.1. ADD DETAIL FOR THIS WALL CONSTRUCTION.
2. SHEET A1.0; FLOOR PLAN: ALL CORRIDOR DOORS MUST MEET THE FIRE RESISTANCE RATING LISTED IN THE 2006 IBC, TABLE 715.4. REVISE THE SCHEDULE ON SHEET A4.0.
3. SHEET A1.0; FLOOR PLAN: PROVIDE A HIGH/LOW DRINKING FOUNTAIN OR SINGLE POINT-OF-USE WATER DISPENSER PER THE 2006 IBC, TABLE 2902.1.
4. SHEET A3.1; ROLL IN SHOWER: A ROLL IN SHOWER REQUIRES GRAB BARS PER THE ICC/ANSI A117.1-2003, SECTION 608.2.2. REVISE THE ELEVATION ON THIS SHEET.
5. SHEET A1.0: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE KEYNOTES.
6. SHEET P2.0; WATER HEATER DETAIL: INCLUDE IN THIS DETAIL HOW THE WATER HEATER IS SUPPORTED, INCLUDING FRAMING MEMBER SIZES AND HOW THEY ARE CONNECTED TO THE STUD WALL.
09/21/2011 PAUL MACHADO ENGINEERING REVIEW Approved
09/21/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
09/21/2011 MARTIN BROWN FIRE REVIEW Approved
09/21/2011 ERIC NEWCOMB ADA REVIEW Passed
09/21/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/06/2011 DROBEY1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
10/06/2011 DELMA ROBEY OUT TO CUSTOMER Completed