Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T11CM03011
Parcel: 13409018E

Review Status: Completed

Review Details: RESUBMITTAL - SITE ALL

Permit Number - T11CM03011
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
12/12/2011 STEVE SHIELDS ZONING REVIEW Approved
12/19/2011 RONALD BROWN H/C SITE REVIEW Denied 1. For all the accessible parking spaces located in front of the existing shops:
a. The original accessible spaces were designed for angle parking. By restriping them on a 90 degree configuration, you have created new accessible parking spaces that now must comply with Section 3409.6 which requires any altered element to comply with Chapter 11 and ICC/ANSI 117.1.
b. Asphalt ramps located in the accessible parking aisles are not code compliant. All accessible parking aisles are to be provided with curb ramps as required by ANSI 117.1, Section 406 and Figure 406.3.
END OF REVIEW
12/23/2011 LOREN MAKUS ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/12/2012 CINDY AGUILAR OUT TO CUSTOMER Completed
01/12/2012 CINDY AGUILAR REJECT SHELF Completed