Permit Number - T11CM02988
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/03/2011 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Approved | |
| 11/03/2011 | DAVE MANN | FIRE | REVIEW | Denied | The Tucson Fire Code Appendix B count all area under roof for the 3600 square feet for sprinklers or a fire hydrant with a capacity of 1750 gpm. Provide a note that sprinklers will be required or show the subdivision water plan can supply 1750 gpm per hydrant. |
| 11/08/2011 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 11/14/2011 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 11/15/2011 | MICHAEL ST. PAUL | ZONING | REVIEW | Denied | Provide complete floor plans for both units. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/05/2011 | FERNE RODRIGUEZ | OUT TO CUSTOMER | Completed |
| 12/05/2011 | SUE REEVES | REJECT SHELF | Completed |