Permit Number: T11CM02976
Parcel: 122140140

Review Status: Completed

Review Details: SITE

Permit Number - T11CM02976
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/22/2011 DAVE MANN FIRE REVIEW Approved
09/26/2011 RONALD BROWN H/C SITE REVIEW Denied 1. Provide reduced vertical clearance at all stairs as per ICC/ANSI 117.1, Section 307.4
2. Please show accessible route slope compliance with ICC/ANSI 117.1, Section 403.3.C/ANSI 117.1, Section 403.3.
3. At detail 2/CVR, please show accessible parking space slope compliance with ICC/ANSI 117.1, Section 502.5
4. Identify accessible parking space and show location of signage on sheet SD-1.
END OF REVIEW
09/27/2011 LAITH ALSHAMI ENGINEERING REVIEW Denied Laith Alshami, Engineering and Floodplain Review, 10/06/2011

Provide the following information on the site plan:

1. Submit a drainage statement that addresses offsite and onsite drainage and its impact on the subject site. Additionally, provide the design calculations for all proposed drainage structures and facilities.
2. PDSD Map shows that the site consists of two lots. It appears that the proposed development will be on both lots, which requires combining both lots. Has a lot combo been processed?
3. Show the future spandrel at Country Club and Fairmount Ave.
4. Provide a property legal description as required by 2-02.1.A.2.
5. The location map does not show the location of site clearly. Revise the location map (2-02.1.A.4).
6. Show all existing buildings and structures, including location, size, height, overhangs, canopies, and use (2-02.1.A.6).
7. Provide additional finished grades especially at the proposed scuppers and drainage structures (2-02.1.A.16).
8. Show, if applicable, all easements of record together with recording docket and page reference (2-02.1.A.20).
9. The proposed refuse container location appears to be inaccessible for curb-side pickup. Additionally, the trash enclosure shall comply with the standard detail in Development Standard 6-01.0. Revise the plan to demonstrate compliance.


Resubmittal Required: Revised Site Plan
09/30/2011 TERRY STEVENS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Terry Stevens
Lead Planner

PROJECT: T11CM02976
3101 E. Fairmount Ave.
Site Plan

TRANSMITTAL DATE: 09/30/11

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. DS 2-02.2.1.A.31 List the proposed use as follows: Family Dwelling "P", subject to: Sec. 3.5.7.1.F

2. This property consists of two separate parcels, therefore a tax parcel combination is required. The form submitted is not complete. It must be signed and approved by the County Assessors office.

3. The above comments are minor in nature and can be reviewed over the counter by setting an appointment with me.

If you have any questions about this transmittal, please call Terry Stevens, (520) 837-4961

C:\planning\cdrc\DSD\T11CM02976.doc
10/05/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
10/13/2011 ANDREW CONNOR LANDSCAPE REVIEW Denied The site plan and landscape plan must show identical site layout to avoid conflict between the two plans. Ensure that all changes to the site plan are reflected on the landscape plan.

Additional comments may apply
10/17/2011 ANDREW CONNOR NPPO REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/27/2011 CPIERCE1 OUT TO CUSTOMER Completed
10/27/2011 SUE REEVES REJECT SHELF Completed