Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM02975
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/16/2011 | TERRY STEVENS | ZONING | REVIEW | Passed | |
| 09/16/2011 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 09/16/2011 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 09/26/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | SHEET C-105 1. As per the 2006 IBC, Section 1106.1, if more than 201 parking spaces are provided, a total number of 7 accessible parking spaces are required. Please provide an additional 3 accessible parking spaces. SHEET G-102 2. Please provide special inspection certifications as outlined in the Special Inspection Schedule. 3. Please reconcile item 4 occupancy load calculation summary with that as item 19 plumbing requirements. SHEET C-015 4. Please provide large scale plan details of all the different accessible parking layouts showing all required accessible dimensions, slopes, aisles, markings "Van Accessible" spaces, access to accessible route, ramps as required and signage. a. Please provide large scale signage detail including "Van Accessible" signage. 5. Please identify accessible route and show slope compliance with ICC/ANSI 117.1, Section 403.3. SHEET C106 6. Please provide structural calculations for the 9' high wrought iron fence and gates. 7. Ditto Comments 4 and 5 above. SHEET A102 8. All the title block scale notation is incorrect for detail 1 through 4. Please correct. 9. The dimensions shown on the toilet stalls and the urinal screen needs to be clear dimensions and not to the partition center line. 10. Please explain how the showers at detail 1 are in compliance with ICC/ANSI 117.1, Section 608. SHEET A 202 11. Please finish the accessible dimensioning both vertical and horizontal, for all toilet room elevations. END OF REVIEW |
| 10/04/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. The minimum insulation for ducts located outside of the building envelope is R-8. Show how the entire supply duct (and return duct) of each A/C unit is provided with this insulation level. Reference: Section 503.2.7, IECC 2006, as amended by the City of Tucson. 2. Verify that the termination of the restroom exhaust from room 121 can be both 10'-0" from the outside air intake of AC-2 and at least 3'-0" from the door. Reference: Section 501.2.1 (3), IMC 2006. |
| 10/04/2011 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 10/04/2011 | ROBERT SHERRY | WATER | REVIEW | Denied | Provide the size of the existing water meter. Reference: Section 106.3.1, IPC 2006. |
| 10/04/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Verify the total connected gas load for AC-6; it is shown P-101 as 125 CFH but is scheduled with a load of 150 CFH on sheet M-301. Reference: Section 106.3.1, IFGC 2006. 2. Clarify the piping insulation requirements as shown in Specification Section 22 07 00, Part 2.2, A, 1. Section 504.5, IECC 2006 requires all pipes in an automatic recirculating hot water system to be insulated with 1" insulation. |
| 10/05/2011 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/21/2011 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 10/21/2011 | SUE REEVES | REJECT SHELF | Completed |