Permit Number: T11CM02971
Parcel: 121070140

Review Status: Completed

Review Details: OTHER

Permit Number - T11CM02971
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/15/2011 DAVE MANN FIRE REVIEW Denied Per NFPA 13, canopy must contain fire sprinklers. Please add note showing fire sprinklers will be included, and a deferred submittal for sprinklers is forthcoming.
09/28/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. There are no construction documents submitted in this package for the actual canopy i.e. specifications, elevations, connections, drainage plan and/or details.
SHEET S200
2. There are four columns shown on the drawings and scheduled as C1-8" standard poles that are not identified on the calculations key plan page 6. These columns may be located by their referenced foundation mark: DF7, DF4, DF5 and DF6 as shown on the key plan.
3. The most Northerly located column on the drawing is scheduled as C1-8" dia. std. pipe column while the calcs, pages 6 and 8, call for a battered steel pipe.
4. As per the drawings, only 2 types of columns are scheduled whereas the calcs call for 3 types of columns, i.e. battered and non battered. Shouldn't 3 types be shown on the drawings?
END OF REVIEW.
09/29/2011 RONALD BROWN ELECTRICAL-COMMERCIAL REVIEW Passed There are no electrical drawings.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/25/2011 CINDY AGUILAR OUT TO CUSTOMER Completed
10/25/2011 SUE REEVES REJECT SHELF Completed