Permit Number: T11CM02963
Parcel: 12709011K

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM02963
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/09/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Comment not addressed. Show the size, routing, and termination of the condensate drains for the new roof top A/C units. Reference: Section 307.2, IMC 2006 as amended by the City of Tucson and Section 814.0, UPC 2006.
2. Comment not resolved; use the default occupant densities for the zone population Section 403.3, IMC 2006, as amended by the City of Tucson allows the use of the ASHRAE 62-1-2004 ventilation calculation procedure provided that the default occupant densities and combined outdoor air rates are used. Reference: ASHRAE Standard 62.1-2004, and Section 403.3, IMC 2006 as modified by the City of Tucson amendments.
11/09/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Comment not resolved. Provide upper terminal cleanouts for the mop sink, the floor drain next to the water heater, the floor drain next to the water filter, and for the urinal. [Original comment: Provide upper terminal cleanouts on horizontal drainage pipes exceeding 5 feet in length. Reference: Section 707.4, UPC 2006.]