Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T11CM02963
Parcel: 12709011K

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM02963
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/03/2011 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied 1) PP G-CS CONSTRUCTION TYPE NOT NOTED PLEASE CLARIFY

2) PP G-LS ERRATA: OFFICE OCCUPANT LOADS ARE 1:100 NOT 1:200---THIS DOES NOT HOWEVER CHANGE OCC LOAD FOR THIS PROJECT

3) PP A1.0 SITE PLAN INDICATES 5892 SQ FT OF LEASE SPACE WHILE COVER SHEET SHOWS 4524. PLEASE CLARIFY

4) PLEASE PROVIDE TOP OF WALL DETAIL FOR 1 HOUR WALL, INCLUDING ANY SLIP REQUIREMENTS FOR BUILDING EXPANSION AND CONTRACTION.

4a) IN LIEU OF TOP OF WALL DETAIL AND 1 HOUR WALL YOU MAY PROVIDE CODE ANALYSIS ON COVER SHEET FOR NON SEPARATED USE AS ALLOWED BY IBC 508.3.2

5) CAUTION: PP A4.1 HAS SANITARY NAPKIN DISPENSORS AT SIDE OF WATER CLOSETS. 15" CLEAR IS REQUIRED FROM CENTER OF WC TO OBSTRUCTIONS PER UPC 407.6. YOU MAY HAVE THIS CLEARANCE IN ACCESSIBLE STALL IF DISPENSOR IS 3" OR LESS IN DEPTH, BUT YOU DO NOT APPEAR TO HAVE IT IN NORMAL STALL.
11/08/2011 CPIERCE1 MECHANICAL-COMMERCIAL REVIEW Needs Review
11/08/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11CM02963
6129 E Broadway


Item 3 last review not provided, The fixture cut sheets alonf with the 2006 IECC Lighting Budget Calculations are required with this set of plans in order to approve. I did notice the note on Sheet E3.1 indicating fixtures to be supplied by owner and installed by contractor, these items still required in order to issue permit.


Ray T Majuta
Electrical Plan Review,
11/8/11
11/08/2011 CPIERCE1 WWM REVIEW Needs Review
11/08/2011 CPIERCE1 ZONING REVIEW Needs Review
11/08/2011 CPIERCE1 PLUMBING-COMMERCIAL REVIEW Needs Review