Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T11CM02963
Parcel: 12709011K

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM02963
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/20/2011 DAVE MANN FIRE REVIEW Approved
09/23/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Need to provide last approved site plan for review.
2. Please provide special inspections certifications as outlined on sheet S-1.0 and S-1.1.
3. Needs health department review.
END OF REVIEW
10/03/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show the size, routing, and termination of the condensate drains for the new roof top A/C units. Reference: Section 307.2, IMC 2006 as amended by the City of Tucson and Section 814.0, UPC 2006.
2. Section 403.3, IMC 2006, as amended by the City of Tucson allows the use of the ASHRAE 62-1-2004 ventilation calculation procedure provided that the default occupant densities and combined outdoor air rates are used. Reference: ASHRAE Standard 62.1-2004, and Section 403.3, IMC 2006 as modified by the City of Tucson amendments.
3. Specify the minimum resistance (R-value) of the duct insulation to be used on this project. Reference: Section 503.2.7, IECC 2006, as amended by the City of Tucson.
10/03/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Appliances (e.g. chemical dispensers) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Table 6-3, UPC 2006 require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 602.3, 603.0, and Table 6-2, UPC 2006.
2. Provide a reduced-pressure-principle backflow prevention assembly for the misting system. Reference: Section 603.4.6.2, UPC 2006.
3. Provide pressure-absorbing devices for the water connections to appliances equipped with quick-acting or solenoid valves. Reference: Section 609.10, UPC 2006.
4. The minimum residual water pressure is 15 PSI. Note that some water closets and some appliances (e.g. ovens, water closets, etc.) require minimum residual pressures greater than 15 PSI. Reference: Section 608.1, UPC 2006.
5. Clarify how the water fixture units have been calculated. If Table 6-5, UPC 2006 has been used, correct the water fixture units for the urinal (20 fixture units per Table 6-7, UPC 2006). If, however, Appendix A, UPC 2006 is being used, reduce the water fixture units for the water closets to 8 fixture units each and use curve 1 on Chart A-3 to determine the water demand. Reference: Sections 610.5 and 610.10, UPC 2006.
6. The domestic water isometric diagram (2/P-3.1) appears to show the water closets served by 1" copper tubing. A flush valve delivers 1.6 gallons in about four seconds which is approximately 24 GPM. This results in a water velocity of 9.3 feet per second in 1" Type L copper. Limit the water velocity to less than 8 FPS for the copper piping. Reference: Sections 610.12 and A 6.1, UPC 2006 and IS 3-2003, Section 2.6.
7. Clarify the location of the proposed new water meter and backflow preventer; Chapter XXVII, Article V, Section 27-72, of the Tucson Code, requires a reduced pressure backflow preventer to be located immediately after the water meter and they are required to be installed in locations accessible to Tucson Water.
8. Provide upper terminal cleanouts on horizontal drainage pipes exceeding 5 feet in length. Reference: Section 707.4, UPC 2006.
9. Show that the floor drains used as indirect receptors for condensate, appliance drains, and T&P relief for the water heater are designed to prevent splashing. Reference: Section 804.1, UPC 2006.
10. Provide protection of the trap seals for all floor drains subject to infrequent use. Reference: Sections 1007.0 and 1007.1, UPC 2006, as amended by the City of Tucson.
10/03/2011 ROBERT SHERRY WATER REVIEW Approved
10/05/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11CM02963
6129 E Broadway Bl
Paradise Bakery and Cafe

Electrical plans denied for following:
1. Sheet E5.1, the service entrance conductoes shold be 4 #600kcmil rather than three, I read the 3/0 G as a ground.
2. The grounding system should be provided with two ground rods in conjunction with what is shown on the grounding system.
3. Provide 2006 IECC Lighting Budget Calculations as required by City of Tucson Submittal Requirements.
4. Provide a fault current method of protection which complies with 2005 NEC 11.22 for the let thru on to the panels which will have ratings above 22 KAIC.

Ray T Majuta
Elect Pln Ck
PDSD, City of Tucson
10/11/11
Ray.majuta@tucsonaz.gov
10/11/2011 GERRY KOZIOL WWM REVIEW Denied need to show exsistiiing locaaation/method of connection to public sewer. - need to show location & size of grease interceptor
need 5th floor credit evaaluation - 740-6602
need capaciity review & app0roval- Kurt Stemm- 740-6607
need wastewater IWC review & approval of greassse interceptor - Tom Tomchak, 5025 W Ina Rd- 443-6200
10/14/2011 MICHAEL ST. PAUL ZONING REVIEW Denied Provide a copy of the last approved site plan and the last C of O (T06OT01213). The outdoor dining appears to be an expansion. A new site plan shall be required if ther is an expansion.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/01/2011 CPIERCE1 OUT TO CUSTOMER Completed
11/01/2011 SUE REEVES REJECT SHELF Completed