Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM02956
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/14/2011 | MARTIN BROWN | FIRE | REVIEW | Denied | Full fire alarm system required due to both tenants using commom path of egress, making combined occupant load over 300. (2006 IFC, section 907) |
09/20/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | SHEET A1.0 1. The occupancy load and space s.f. areas do not add up. a. Total occupants adds up to be 443 not 410 b. Total project area s.f. including future patio adds up to be 10,970 not 10,817 c. Please reconcile both errors. 2. On your General Building Summary for Space 270 is identified as a restaurant A2 when in fact it is a kitchen with out a dining area, "F-1" occupancy classification. 3. In your project data summary Tenant 270-Chocolate Fox Kitchen Aera, the correct Occupancy Classification should be "F-1" not "B". A restaurant without a dining area is a food factory. GENERAL 4. Please provide structural calculations for all roof top mounted HVAC equipment. END OF REVIEW |
09/27/2011 | GERRY KOZIOL | WWM | REVIEW | Denied | NEED TO IDENTIFY ALL WASTEWATER PLUMBING FIXTURES: EXSISTING, REMOVED OR RELOCATED FOR CREDIT. |
09/29/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | The size of the gas main and the branch for the future gas range appear to be incorrect; provide gas pipe sizing calculations demonstrating conformance to Section 402.1 and 402.3, IFGC 2006. |
09/29/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
09/30/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show how the fan coil is being connected to the building structure and provide calculations to show that the building structure is not being adversely affected. Reference: Section 302.1, IMC 2006. 2. Provide structural calculations and details to show that the Type I hood is supported from the building structure in accordance with Section 507.6, IMC 2006. Reference: Section 302.1, IMC 2006. 3. Show that the hood installation complies with Section 507.9, IMC 2006 for clearances (e.g. wall construction, combustibles within the walls, etc). |
10/05/2011 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Denied | |
10/06/2011 | MICHAEL ST. PAUL | ZONING | REVIEW | Denied | A stamped approved site plan is required; per David Rivera. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
10/11/2011 | DELMA ROBEY | OUT TO CUSTOMER | Completed |