Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM02955
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/14/2011 | MARTIN BROWN | FIRE | REVIEW | Denied | Full fire alarm system required due to both tenants using commom path of egress, making combined occupant load over 300. (2006 IFC, section 907) |
09/20/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | SHEET A1.0 1. The occupancy load and space s.f. areas do not add up. a. Total occupants adds up to be 443 not 410 b. Total project area s.f. including future patio adds up to be 10,970 not 10,817 c. Please reconcile both errors. 2. On your General Building Summary for Space 270 is identified as a restaurant A2 when in fact it is a kitchen with out a dining area, "F-1" occupancy classification. 3. In your project data summary Tenant 270-Chocolate Fox Kitchen Aera, the correct Occupancy Classification should be "F-1" not "B". A restaurant without a dining area is a food factory. GENERAL 4. Please provide structural calculations for all roof top mounted HVAC equipment. END OF REVIEW |
09/27/2011 | GERRY KOZIOL | WWM | REVIEW | Denied | NEED TO IDENTIFY ALL WASTEWATER PLUMBING FIXTURES: EXSISTING, REMOVED OR RELOCATED FOR CREDIT. |
09/29/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
09/29/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
09/30/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show the location of the water heater vent on the roof plan. Show that it complies with the termination requirements of Section 503.8 (3), IFGC 2006. 2. Show how the fan coils are being connected to the building structure and provide calculations to show that the building structure is not being adversely affected. Reference: Section 302.1, IMC 2006. 3. Show how the gas-fired radiant heating units are being connected to the building structure. Reference: Section 302.1, IMC 2006 |
10/03/2011 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Denied | COULD NOT COMPLETE REVIEW WITH THIS SET OF PLANS. THIS IS NOT A REVISION TO THE PREVIOUS PERMIT FOR 278 E. CONGRESS "AN CONGRESS", BUT SHOULD A SEPARATE AND SELF STANDING ACTIVITY. PLEASE SUBMIT ELECTRICAL DRAWINGS FOR PROPOSED TI WORK FOR UNITS 270 & 278 ONLY. DELETE ALL REFERENCES TO "NEW" WORK THAT HAS BEEN INSTALLED UNDER PREVIOUS ACTIVITY FOR "AN CONGRESS" AND IS THERFORE EXISTING. |
10/06/2011 | MICHAEL ST. PAUL | ZONING | REVIEW | Denied | A stamped approved site plan is required; per David Rivera. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
10/11/2011 | DELMA ROBEY | OUT TO CUSTOMER | Completed |