Permit Number: T11CM02916
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM02916
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/09/2011 DAVID RIVERA ZONING REVIEW Denied On the overall site plan, depict, highlight, and label the location of suite 292.
09/09/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. The governing codes are the 2006 International Mechanical Code, including local amendments and the 2006 International Energy Conservation Code.
2. All supply and return air ducts and plenums shall be insulated with a minimum of R-4.2 insulation when located in indirectly conditioned spaces. Reference: Section 503.2.7, IECC 2006, as amended by the City of Tucson.
09/09/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Needs Review
09/09/2011 ROBERT SHERRY WATER REVIEW Approved
09/09/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. GENERAL: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE.
2. SHEET C1; PROJECT INFORMATION: CURRENT CODE IS THE 2006 IBC. REVISE.
3. SHEET C1; PROJECT INFORMATION: LIST THE CURRENT ACCESSIBILITY CODE AS THE ICC/ANSI A117.1-2003.
4. SHEET A5; ELEVATION 6: PROVIDE A VERTICAL GRAB BAR PER ICC/ANSI A117.1-2003, FIGURE 604.5.1.
09/09/2011 GERRY KOZIOL WWM REVIEW Approved
09/09/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The governing code is the 2006 Uniform Plumbing Code, including local amendments
2. Revise the size of the cleanout per Table 7-6, UPC 2006. Reference: Section 707.11, UPC 2006.
09/09/2011 LOREN MAKUS ENGINEERING REVIEW Approved
09/09/2011 CPIERCE1 FIRE REVIEW Needs Review
09/09/2011 ERIC NEWCOMB ADA REVIEW Passed
09/09/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed