Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM02916
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/09/2011 | DAVID RIVERA | ZONING | REVIEW | Denied | On the overall site plan, depict, highlight, and label the location of suite 292. |
| 09/09/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. The governing codes are the 2006 International Mechanical Code, including local amendments and the 2006 International Energy Conservation Code. 2. All supply and return air ducts and plenums shall be insulated with a minimum of R-4.2 insulation when located in indirectly conditioned spaces. Reference: Section 503.2.7, IECC 2006, as amended by the City of Tucson. |
| 09/09/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 09/09/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 09/09/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. GENERAL: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE. 2. SHEET C1; PROJECT INFORMATION: CURRENT CODE IS THE 2006 IBC. REVISE. 3. SHEET C1; PROJECT INFORMATION: LIST THE CURRENT ACCESSIBILITY CODE AS THE ICC/ANSI A117.1-2003. 4. SHEET A5; ELEVATION 6: PROVIDE A VERTICAL GRAB BAR PER ICC/ANSI A117.1-2003, FIGURE 604.5.1. |
| 09/09/2011 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 09/09/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The governing code is the 2006 Uniform Plumbing Code, including local amendments 2. Revise the size of the cleanout per Table 7-6, UPC 2006. Reference: Section 707.11, UPC 2006. |
| 09/09/2011 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 09/09/2011 | CPIERCE1 | FIRE | REVIEW | Needs Review | |
| 09/09/2011 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 09/09/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |