Permit Number: T11CM02898
Parcel: 12510003F

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T11CM02898
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/25/2013 KEN BROUILLETTE FIRE REVIEW Approved
02/26/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
03/04/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
03/05/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Under the accessories heading of the toilet plumbing fixture schedule on sheet P2, lavatories L6, L8, and L10 are noted as not requiring the installation of a temperature mixing valve. Show how the water temperature will be limited to 110degrees Fahrenheit if the mixing valves are omitted. Reference: Section 504.3, IECC 2006 and Section 413.1, UPC 2006.
2. The 3-compartment sink, SS023, in the deli prep area appears to have only an indirect waste connection. Provide direct waste connections for the wash and rinse sections of the 3-compartment sink, with an indirect connection for the sanitizing compartment only. See detail 3/GP2. Reference: Sections 304.0, 704.3, and 801.2.3, UPC 2006.
03/05/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/03/2013 SHANAE POWELL APPROVAL SHELF Completed
04/03/2013 SHANAE POWELL OUT TO CUSTOMER Completed