Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T11CM02898
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/25/2013 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
02/26/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
03/04/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
03/05/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Under the accessories heading of the toilet plumbing fixture schedule on sheet P2, lavatories L6, L8, and L10 are noted as not requiring the installation of a temperature mixing valve. Show how the water temperature will be limited to 110degrees Fahrenheit if the mixing valves are omitted. Reference: Section 504.3, IECC 2006 and Section 413.1, UPC 2006. 2. The 3-compartment sink, SS023, in the deli prep area appears to have only an indirect waste connection. Provide direct waste connections for the wash and rinse sections of the 3-compartment sink, with an indirect connection for the sanitizing compartment only. See detail 3/GP2. Reference: Sections 304.0, 704.3, and 801.2.3, UPC 2006. |
03/05/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
04/03/2013 | SHANAE POWELL | APPROVAL SHELF | Completed |
04/03/2013 | SHANAE POWELL | OUT TO CUSTOMER | Completed |