| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/01/2012 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 02/02/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Comment not resolved. Correct the size of the combined condensate drains in accordance with Section 307.2.1, IMC 2006, as amended by the City of Tucson. Specifically: downstream of RTU-8 (40 tons = 1-1/4"), downstream of RTU-5 (100.5 tons = 2"), downstream of the junction of RTU-10 and RTU-13 (30 tons = 1-1/4"), the main condensate line downstream of the junction with RTU units 10, 12, and 13 (117.5 tons = 2") and the final condensate main near column G-3 (137.5 tons = 2"). [Second comment: Comment not resolved. Correct the condensate pipe sizes for rooftop units 3, 10, 14, 15, and 19 (see detail4/P1 for note regarding the size of condensate drains for single rooftop units and air handling units). Correct the size of combined condensate drains based on the requirements of Section 307.2.1, IMC 2006, as amended by the City of Tucson.] [Original comment: Revise the size of the condensate drains in accordance with Section 307.2.1, IMC 2006, as amended by the City of Tucson. Show all the pipe sizes on the drawing. Note that the minimum pipe size for a condensate drain is ¾" or the size of the drain pan connection, whichever is larger.] |
| 02/02/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved |