Permit Review Detail
Review Status: Completed
Review Details: SITE
Permit Number - T11CM02884
Review Name: SITE
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/12/2012 | MARTIN BROWN | FIRE | REVIEW | Passed | |
| 01/12/2012 | DAVID RIVERA | NPPO | REVIEW | Approved | |
| 01/12/2012 | DAVID RIVERA | LANDSCAPE | REVIEW | Approved | |
| 01/12/2012 | RONALD BROWN | H/C SITE | REVIEW | Passed | |
| 01/12/2012 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 01/12/2012 | RBROWN1 | ADA | REVIEW | Passed | |
| 01/12/2012 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 02/02/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Revise the site drawing to include the following information: a. the size of the water meter b. the location and size of the public sanitary sewer c. the location of the building connection to the public sewer d. the location, invert, and rim elevation of the upstream and downstream manholes e. the first floor elevation for each building Reference: City of Tucson Development Standard No. 2-01.0.0, Section 3.8 D and Section 103.2.3, UPC 2006. 2. Reduced pressure backflow prevention assemblies are required at the water meter for properties with sub-meters. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://cms3.tucsonaz.gov/sites/default/files/water/docs/backflow-ordinance.pdf |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/13/2012 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |