Permit Number: T11CM02884
Parcel: 129020100

Review Status: Completed

Review Details: SITE

Permit Number - T11CM02884
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/12/2012 MARTIN BROWN FIRE REVIEW Passed
01/12/2012 DAVID RIVERA NPPO REVIEW Approved
01/12/2012 DAVID RIVERA LANDSCAPE REVIEW Approved
01/12/2012 RONALD BROWN H/C SITE REVIEW Passed
01/12/2012 DAVID RIVERA ZONING REVIEW Approved
01/12/2012 RBROWN1 ADA REVIEW Passed
01/12/2012 LOREN MAKUS ENGINEERING REVIEW Approved
02/02/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Revise the site drawing to include the following information:
a. the size of the water meter
b. the location and size of the public sanitary sewer
c. the location of the building connection to the public sewer
d. the location, invert, and rim elevation of the upstream and downstream manholes
e. the first floor elevation for each building
Reference: City of Tucson Development Standard No. 2-01.0.0, Section 3.8 D and Section 103.2.3, UPC 2006.
2. Reduced pressure backflow prevention assemblies are required at the water meter for properties with sub-meters. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://cms3.tucsonaz.gov/sites/default/files/water/docs/backflow-ordinance.pdf

Final Status

Task End Date Reviewer's Name Type of Review Description
02/13/2012 CINDY AGUILAR OUT TO CUSTOMER Completed