Review Date Reviewer's Name Type of Review Description Status Comments
12/19/2011 GERRY KOZIOL WWM REVIEW Approved
12/29/2011 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 12-29-11
Activity: T11CM02884
Address: 300 S Country Club
Applicant: Ric Espiriti

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

PLUMBING PLAN:
1. Provide the maximum developed length of water line from the meter the furthest appliance served, the diameter of the water service line, and the lowest available pressure after pressure loss calculations, P2903.7.
2. Provide a water fixture unit schedule for the entire property (including existing) P2903.6.
3. Provide note requiring that water hammer arrestor be installed in accordance with ASSE 1010-2004 on water lines serving appliances equipped with quick-closing valves to include but not limited to: clothes washers, dishwashers, and refrigerators, IRC P2903.5.

MECHANICAL PLAN:
4. Show supply and return air ducts with a minimum R-8 insulation when located outside the thermal envelope, R1103.2.1.

ELECTRICAL PLAN:
5. Designate the circuit number for the smoke detectors and specify arc-fault protection, E3603.5.
6. Notate that smoke detectors must be interconnected with a power source from the building wiring, and shall be equipped with battery backup, R313.
7. Island or peninsula counter tops with a long dimension of 24” and a short dimension of 12” or greater shall have at least one receptacle, E3801.4.2.
8. Bathrooms receptacles require a separate 20-amp circuit, E3603.4, E3801.6.
9. Exterior outlets at grade level shall be provided at both the front and back of the dwelling, E3801.7. These outlets shall be GFCI protected E3802.3.
10. Convenience receptacles and light switches/fixtures shall be provided within 25’ of mechanical equipment, E3801.11, E3803.4.
11. Size feeder conductors according to Table E3503.1 for proposed service panel capacities.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
02/13/2012 CINDY AGUILAR OUT TO CUSTOMER Completed