Permit Number: T11CM02883
Parcel: 11706081A

Address:
290 E 8TH ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM02883
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/13/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied See comments for T11CM02699 for 10/12/11

Ray T Majuta
10/12/11
10/14/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a plumbing design for the wash bay, including the water source, the drainage fixtures and piping, and sand-oil separator plans. Revise the site utility drawing (C2.4) to include this structure. Reference: Section 103.2.3, UPC 2006.
2. The washing equipment specifications call for a minimum water pressure of 40 PSIG. With a site water pressure of only 46 PSIG prior to the water meter and backflow preventer, will a booster pump be required? Provide water pressure calculations and determine the equipment water demand. Assuming that only one water meter serves the site, determine if the total demand for the site exceeds 80 GPM; revise the size of the proposed water meter or add a second water meter to serve the wash bay. Reference: Sections 608.1, 609.8, and 610.2, UPC 2006.
3. Provide backflow protection for equipment directly connected to the water distribution system within the wash bay. Reference: Section 602.0, UPC 2006.
4. Revise the rain gutter sizing for the wash bay based on a storm of 60-minutes duration and a 100-year return period, i.e. 3" per hour. Reference: Section 1101.11.1 and Table 11-3, UPC 2006.
10/14/2011 RONALD BROWN ADA REVIEW Approved
10/14/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
10/14/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
11/02/2011 LOREN MAKUS ENGINEERING REVIEW Needs Review